FX2N-48MR-UA1/UL Mitsubishi PLC

Category: .
Ambient temperature 0 ~ 55 ℃ ・ ・ ・ Operating, -20 ~ 70 ℃ ・ ・ ・ Storage
Relative humidity 35% to 85% (with no condensation): Operating
Vibration resistance When mounting DIN rail Frequency: 10-57Hz Half amplitude: 0.035 mm X, Y, Z each direction 10 times (total each 80 minutes)
criteria, according to IEC61131-2
Frequency: 57-150Hz Acceleration: 4.9 m / s 2 X, Y, Z each direction 10 times (total each 80 minutes)
criteria, according to IEC61131-2
Direct mounting Frequency: 10-57Hz Half amplitude: 0.075 mm X, Y, Z each direction 10 times (total each 80 minutes)
criteria, according to IEC61131-2
Frequency: 57-150Hz Acceleration: 9.8m / s 2 10 times in each of the X, Y, and Z directions (total of 80 minutes each)
Judgment criteria are based on IEC61131-2
Shock resistance 147m / s 2 , working time 11ms, sinusoidal half-wave pulse 3 times each in X, Y, Z directions
Judgment criteria are according to IEC61131-2
Noise resistance Using a noise simulator with a noise voltage of 1,000 Vp-p,
a noise width of 1 μs, a rise of 1 ns, and a period of 30 to 100 Hz
Withstand voltage When performing a withstand voltage test, perform the following voltage between each terminal and the ground terminal of the basic unit.
Between power supply terminal (AC power supply) and ground terminal: AC1.5kV for 1 minute Between
input terminal (AC100V) and ground terminal: AC1.5kV for 1 minute Between
output terminal (relay) and ground terminal: AC1.5kV for 1 minute
Insulation resistance When performing an insulation resistance test, perform the following voltage between each terminal and the ground terminal of the basic unit.
Between power supply terminal (AC power supply) and ground terminal: 5 MΩ or more with DC500V insulation resistance meter Between
input terminal (AC100V) and ground terminal: 5MΩ or more with DC500V insulation resistance meter Between
output terminal (relay) and ground terminal: DC500V insulation resistance 5MΩ or more in total
ground Class D grounding (Grounding resistance: 100Ω or less) <Cannot be shared with high-voltage systems> Use
a dedicated or shared ground for grounding.
Usage atmosphere There is no corrosive or flammable gas, and the conductive
dust (dust) is not severe.
Usage altitude Cannot be used in an environment pressurized to 2000m or less
and atmospheric pressure. There is a possibility of failure.