Placeholder
FX2N-4DAFX2N-4DA

FX2N-4AD Mitsubishi PLC

Category: .
Analog output Analog output range Voltage output DC-10V to + 10V (External load resistance 2kΩ to 1MΩ)
Current output DC 0mA to + 20mA (External load resistance 500Ω or less)
Number of output channels 4 channels
Output characteristics The output mode (voltage / current output) can be set for each channel.
Digital input Voltage output 11bit binary + sign 1bit
Current output 10bit binary (unsigned)
resolution Voltage output 5mV (10V x 1/2000)
Current output 20μA (20mA × 1/1000)
Overall accuracy Voltage output ± 1% (± 0.2V) for full scale 20V (Excluding
load fluctuation)
Current output ± 1% (± 0.2 mA) for full scale 20 mA
D / A conversion time 2.1ms / 4 channels (regardless of the number of channels used)
Insulation method The analog output section and sequencer are isolated by a photocoupler
The analog output section and power supply are isolated by a DC / DC converter
Each channel is not isolated
Number of occupied I / O points 8 points (can be counted by either input or output)
Applicable sequencer FX2N, FX3U, FX2NC, FX3UC
<Connecting to the connector type sequencer>
FX2NC-CNV-IF is required to connect to FX2NC.
FX2NC-CNV-IF or FX3UC-1PS-5V is required for connection to FX3UC.
mass 0.3kg
Power supply specifications
Power supply 5V 30mA (Internal power supply from PLC)
DC24V ± 10% 200mA (External power supply)

Reviews